EXcite™ Manual Call Point BCP135

BCP135.....

Features

  • Break glass type
  • Lift flap available as option
  • Optional LED indicator

Marking

ATEX:
Ex II 2 G Ex d IIB+H2 T6 Gb
Ex II 2 G Ex tb IIIC T85˚C, IP66
IECEx:
Ex tb IIIC T85˚C, IP66

Guidelines/Norms

EN 60079-0:2012 (IEC 60079-0:2011),
EN 60079-1:2007 (IEC 60079-1:2007),
EN 60079-31:2009 (IEC 60079-31:2008)
and EN 54

Ambient temperature

-40 ˚C to +70 ˚C (-40 °F to +158 °F)

Certification

PRESAFE 14 ATEX 5385X
IECEx PRE 14.0047X

Description

BCP135 Ex Manual Call Point is designed according to ATEX and IECEx standards. It especially applies to Oil & Gas, Chemical, Petrochemical, Refinery, Marine and Offshore Industries for the high-corrosion and hazardous areas. It is compatible with PLC, DCS and ESD system via 4-20 mA output. It is ideal to be used as an ex Manual Call Point for fire alarm system with addressable module fixed.

The design of two LED indicators (Green and/or Red) is unique. During normal operation, the green LED is on. When device fault or alarm status arises, the green LED will be cut off and red LED will be on. We provide colors of Red (RAL3001), Yellow (RAL1003) and Blue (RAL5005) for customer’s selection.


Technical data *

Protection class IP66
Dimensions L: 135 mm / 5.31″
W: 135 mm / 5.31″
H: 80.5 mm / 3.17″
Material Enclosure: GRP
Weight 1.5 kg / 3.31 lbs
Connection Terminal: up to 2,5 mm2 cable
Cable Entry: 2 x M20, 1 gland (COD: 9-16) and 1 plug is standard

*Refer to the documentation for more detailed information


Documentation

Data Sheet - EXcite™ Manual Call Point BCP135

EC-Declaration of Conformity EXcite BCP135

User Manual BCP135