Measuring transducer for Pt100 galvanically isolated

07-7311-93T5/.350

Features

  • For Pt100
  • Analog output 4 to 20 mA
  • Fault detector
  • Ex ia/ib
  • Two-, three-wire senors
  • EMV according to
    DIN EN 61000-6-3: 2007;
    DIN EN 61000-6-4: 2007;
    DIN EN 61000-6-1: 2007;
    DIN EN 61000-6-2: 2006

Marking

Ex II 2G Ex db e [ia Ga] IIC Gb
Ex I M2 Ex db e [ia Ma] I Mb
Ex db e [ia Ga] IIC/IIB Gb
Ex db e [ia Ma] I Mb
Class I, Zone 1, IIC
A/Ex d e [ia] IIC Gb

Guidelines/Norms

Directive 2004/108/EC
Directive 94/9/EC

Ambient temperature

-40 °C to +60 °C at T4

Certification

PTB 97 ATEX 1068 U
TÜV 97 ATEX 1204 X
IECEx PTB 11.0083U
IECEx TUN 11.0030X
CSA 2484303
TC RU C-DE.BH02.B.00005
UL-BR 14.0331X

Description

The MODEX series includes a temperature measuring transducer mounted on-site in the same way as a rail-mounted terminal. The module transforms the signal received from the Pt100 temperature sensor into a proportional, load independent 4 to 20 mA output signal. The sensor circuit is intrinsically safe according to Ex protection type Ex ia. An output current exceeding the 4 to 20 mA range signals a senor fault (open/short circuit). The Pt100 temperature sensor can be operated in 2-wire or 3-wire circuits in Zone 0 or Zone 1.


Technical data *

Protection class Module: IP 66/IEC 60529
Terminals: IP 20/IEC 60529
Material High-quality thermoplastic
Installation TH 35 x 15 (7.5) EN/IEC 60715
Storage temperature -40 °C to +60 °C
Weight 0.250 kg
Temperature range -50 °C to +400 °C (see data sheet)
Voltage DC 24 V -10 %/+20 %
Output current Load independent current: 4 to 20 mA
Power Power consumption: 1.6 W
Connection Terminals 2.5 mm², fine stranded

*Refer to the documentation for more detailed information


Documentation

Data Sheet - Measuring transducer for Pt100 galvanically isolated

Declaration of Conformity 01-7311-7C0030